Dryer Vent Safety
by Nick Gromicko, Rob London and Kenton Shepard
Clothes dryers evaporate the water from wet clothing by blowing
hot air past them while they tumble inside a spinning drum. Heat is
provided by an electrical heating element or gas burner. Some heavy
garment loads can contain more than a gallon of water which, during the
drying process, will become airborne water vapor and leave the dryer and
home through an exhaust duct (more commonly known as a dryer vent).
A vent that exhausts moist air to the home exterior has a number
of requirements:
- It should be connected. The connection is usually behind
the dryer but may be beneath it. Look carefully to make sure it’s
actually connected!
- It should not be restricted. Dryer vents are often made
from flexible plastic or metal duct, which may be easily kinked or
crushed where they exit the dryer and enter the wall or floor. This
is often a problem since dryers tend to be tucked away into small
areas with little room to work. Vent hardware is available which is
designed to turn 90° in a limited space without restricting the flow
of exhaust air. Restrictions should be noted in the inspector's
report. Airflow restrictions are a potential fire hazard!
- One of the reasons that restrictions are a potential fire
hazard is that, along with water vapor evaporated out of wet
clothes, the exhaust stream carries lint – highly flammable
particles of clothing made of cotton and polyester. Lint can
accumulate in an exhaust duct, reducing the dryer’s ability to expel
heated water vapor, which then accumulates as heat energy within the
machine. As the dryer overheats, mechanical failures can trigger
sparks, which can cause lint trapped in the dryer vent to burst into
flames. This condition can cause the whole house to burst into
flames! Fires generally originate within the dryer but spread by
escaping through the ventilation duct, incinerating trapped lint,
and following its path into the building wall.
House fires caused by dryers are far more common than generally
believed, a fact that can be appreciated upon reviewing statistics from
the National Fire Protection Agency. Fires caused by dryers in 2005 were
responsible for approximately 13,775 house fires, 418 injuries, 15
deaths, and $196 million in property damage. Most of these incidents
occur in residences and are the result of improper lint cleanup and
maintenance. Fortunately, these fires are very easy to prevent.
The recommendations outlined below reflect International
Residential Code (IRC) SECTION M1502 CLOTHES DRYER EXHAUST guidelines:
M1502.5 Duct construction. Exhaust
ducts shall be constructed of minimum 0.016-inch-thick (0.4 mm)
rigid metal ducts, having smooth interior surfaces, with joints
running in the direction of air flow. Exhaust ducts shall not be
connected with sheet-metal screws or fastening means which extend
into the duct.
This means that the flexible, ribbed vents used in the past should
no longer be used. They should be noted as a potential fire hazard if
observed during an inspection.
M1502.6 Duct length.
The maximum length of a clothes dryer exhaust duct shall not
exceed 25 feet (7,620 mm) from the dryer location to the wall or
roof termination. The maximum length of the duct shall be reduced
2.5 feet (762 mm) for each 45-degree (0.8 rad) bend, and 5 feet
(1,524 mm) for each 90-degree (1.6 rad) bend. The maximum length of
the exhaust duct does not include the transition duct.
This means that vents should also be as straight as possible and
cannot be longer than 25 feet. Any 90-degree turns in the vent reduce
this 25-foot number by 5 feet, since these turns restrict airflow.
A couple of exceptions exist:
- The IRC will defer to the manufacturer’s instruction, so if the
manufacturer’s recommendation permits a longer exhaust vent, that’s
acceptable. An inspector probably won’t have the manufacturer’s
recommendations, and even if they do, confirming compliance with
them exceeds the scope of a General Home Inspection.
- The IRC will allow large radius bends to be installed to
reduce restrictions at turns, but confirming compliance requires
performing engineering calculation in accordance with the ASHRAE
Fundamentals Handbook, which definitely lies beyond the scope of a
General Home Inspection!
M1502.2 Duct termination.
Exhaust ducts shall terminate on the outside of the
building or shall be in accordance with the dryer manufacturer’s
installation instructions. Exhaust ducts shall terminate not
less than 3 feet (914 mm) in any direction from openings into
buildings. Exhaust duct terminations shall be equipped with a
backdraft damper. Screens shall not be installed at the duct
termination.
Inspectors will see many dryer vents terminate in crawlspaces or
attics where they deposit moisture, which can encourage the growth of
mold, wood decay, or other material problems. Sometimes they will
terminate just beneath attic ventilators. This is a defective
installation. They must terminate at the exterior and away from a door
or window! Also, screens may be present at the duct termination and can
accumulate lint and should be noted as improper.
M1502.3 Duct size. The diameter of the
exhaust duct shall be as required by the clothes dryer’s listing and
the manufacturer’s installation instructions.
Look for the exhaust duct size on the data plate.
M1502.4 Transition ducts.
Transition ducts shall not be concealed within construction.
Flexible transition ducts used to connect the dryer to the exhaust
duct system shall be limited to single lengths not to exceed 8 feet
(2438 mm), and shall be listed and labeled in accordance with UL
2158A.
In general, a home inspector will not know specific manufacturer’s
recommendations or local applicable codes and will not be able to
confirm the dryer vent's compliance to them, but will be able to point
out issues that may need to be corrected.